Troubleshooting by Remote Controller Si20-701_B
97
Troubleshooting
NO
YES
NO
Is the
wiring from
the fan motor
securely connected to
connectors on the
indoor unit
PCB?
Connect the
wiring and turn
ON again.
YES
Fix the wiring
and turn ON
again.
Caution
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
may be damaged.
YES
Does the fan
motor run?
Replace the
indoor unit PCB.
Wiring
between the
indoor unit PCB
and fan motor is
disconnected.
Replace the fan
motor.
NO