EasyManuals Logo

Daikin FUY71FJV1 User Manual

Daikin FUY71FJV1
501 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #156 background imageLoading...
Page #156 background image
Troubleshooting by Remote Controller Si20-701_B
149
Troubleshooting
Note:
∗1. HPS activating value is approximately 3.0 MPa.
Is protection
HPS connected to
outdoor unit
PCB?
NO
YES
Correct the
connection.
Is there
continuity in
protection HPS?
NO
YES
Replace the
open-circuit HPS.
Is high
pressure
abnormally high during
operation? (∗1)
YES
Defective
refrigerant
system.
Turn OFF the power.
Wait 2 to 3 minutes after
compressor stops
operating, then check the
following.
NO
Replace the
outdoor unit
PCB.
Caution
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
may be damaged.

Table of Contents

Other manuals for Daikin FUY71FJV1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FUY71FJV1 and is the answer not in the manual?

Daikin FUY71FJV1 Specifications

General IconGeneral
BrandDaikin
ModelFUY71FJV1
CategoryAir Conditioner
LanguageEnglish

Related product manuals