EasyManuals Logo

Daikin FUY71FJV1 User Manual

Daikin FUY71FJV1
501 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #215 background imageLoading...
Page #215 background image
Si20-701_B Troubleshooting by Remote Controller
208
Troubleshooting
Refer to P.473.
The
error is displayed
again.
YES
NO
Is the
electronic
expansion valve
connector properly
connected to the
outdoor unit
PCB?
NO
YES
YES
Connect
properly.
Turn OFF the power
supply and turn the power
ON.
Caution
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
may be damaged.
A
Is the coil resistance
of the electronic
expansion valve
normal?
NO
Replace the
electronic
expansion valve
coil.
CHECK 8
CHECK 8

Table of Contents

Other manuals for Daikin FUY71FJV1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FUY71FJV1 and is the answer not in the manual?

Daikin FUY71FJV1 Specifications

General IconGeneral
BrandDaikin
ModelFUY71FJV1
CategoryAir Conditioner
LanguageEnglish

Related product manuals