EasyManuals Logo

Daikin FUY71FJV1 User Manual

Daikin FUY71FJV1
501 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #219 background imageLoading...
Page #219 background image
Si20-701_B Troubleshooting by Remote Controller
212
Remote Controller Display
F3
Applicable Models
R(Y)-LU, RR-M
Method of Error Detection
The error is detected according to temperature detected
by discharge pipe thermistor.
Error Decision Conditions
îš„ When discharge pipe temperature becomes
abnormally high
îš„ When discharge pipe temperature rises suddenly
îš„ When the discharge pipe thermistor comes out of its
installed position
Supposed Causes
îš„ Improper amount of refrigerant
îš„ Refrigerant piping circuit clogging
îš„ Discharge pipe thermistor comes off the discharge
pipe port
îš„ Electronic expansion valve coil is disconnected from
valve body
îš„ Compressor lead wire has lack of phase

Table of Contents

Other manuals for Daikin FUY71FJV1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FUY71FJV1 and is the answer not in the manual?

Daikin FUY71FJV1 Specifications

General IconGeneral
BrandDaikin
ModelFUY71FJV1
CategoryAir Conditioner
LanguageEnglish

Related product manuals