EasyManuals Logo

Daikin FUY71FJV1 User Manual

Daikin FUY71FJV1
501 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #315 background imageLoading...
Page #315 background image
Si20-701_B Troubleshooting by Remote Controller
308
Note:
∗1. When operating compressor with compressor output
line disconnected, the compressor stops due to error
after elapsed time of 5 seconds. Therefore, check the
voltage increase for 5 seconds.
Refer to P.464.
YES
YES
CHECK 4
Continuity check
in the power transistor
(IGBT). Is the
continuity
normal?
NO
Compressor
inspection.
Inspect
according to the
diagnosis
procedure for
abnormal noises,
vibration,
operating status,
etc. of the
compressor.
Replace the
outdoor unit
PCB.
Is the
inverter
output voltage
generated
approximately at the
same increasing speed
on each phase after
turning ON
again? (∗1)
(U-V, V-
W, W-
U)
NO
Replace the
outdoor unit
PCB.
A
CHECK 4

Table of Contents

Other manuals for Daikin FUY71FJV1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FUY71FJV1 and is the answer not in the manual?

Daikin FUY71FJV1 Specifications

General IconGeneral
BrandDaikin
ModelFUY71FJV1
CategoryAir Conditioner
LanguageEnglish

Related product manuals