Si20-701_B Troubleshooting by Remote Controller
366
Troubleshooting
A
Disconnect the cable from
the compressor, and then
check the compressor for
the insulation resistance.
Check for
power supply
voltage. Voltage
between phases: 380 to
415V Phase
voltage: 220
to 240V
NO
The
insulation
resistance is low (i.e.,
not more than
100kΩ.)
Unbalanced
power supply? (Not
more than 2%: Phase
voltage of not more
than approx.
5V)
On-site causes.
Make proper
wire connections
without open
phase,
erroneous
connections, or
erroneous order
of phases.
On-site causes
Correct the
unbalanced
loads to
eliminate the
unbalanced
state.
Unbalanced
voltage will
cause extremely
unbalanced
current, thus
impairing the
service life of or
resulting in the
error of the
equipment.
NO
YES
YES
Disconnect the cable from
the fan, and then check
the fan motor for the
insulation resistance.
NO
NO
NO
YES
Power
ON
Power
OFF
Replace the
compressor .
Caution
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
may be damaged.

Table of Contents

Other manuals for Daikin FUY71FJV1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FUY71FJV1 and is the answer not in the manual?

Daikin FUY71FJV1 Specifications

General IconGeneral
Cooling Capacity7.1 kW
Heating Capacity8.0 kW
RefrigerantR32
Indoor Unit Dimensions (W x H x D)998 x 310 x 292 mm
Outdoor Unit Dimensions (W x H x D)870 x 734 x 373 mm
Outdoor Unit Weight50 kg
Energy Efficiency Ratio (Cooling)3.21
Energy Efficiency Ratio (EER)3.21
Power Supply220-240V, 50Hz, 1-Phase