Troubleshooting by Remote Controller Si20-701_B
411
Troubleshooting
All
indoor PCB
micro-computer
monitors
blink.
Using 2-
remote controllers
control.
NO
NO
Replace the indoor unit
PCB, and then restart.
YES
YES
SS1 of
both remote
controllers is set to
"MAIN."
Set one remote
controller to
"SUB"; turn the
power supply
OFF once and
then restart.
YES
YES
NO
NO
NO
NO
Operation
returns to normal
when the power is
turned OFF
momentarily.
Replace the
indoor unit PCB.
NO
YES
There is
possibility of
error caused by
noise. Check the
surrounding area
and turn ON
again.
Normal
Normal
There is
possibility of
error caused by
noise. Check the
surrounding area
and turn ON
again.
Replace the remote
controller and restart
operation.
Is it
normal?
Is it
normal?
YES
Caution
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
may be damaged.

Table of Contents

Other manuals for Daikin FUY71FJV1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FUY71FJV1 and is the answer not in the manual?

Daikin FUY71FJV1 Specifications

General IconGeneral
BrandDaikin
ModelFUY71FJV1
CategoryAir Conditioner
LanguageEnglish

Related product manuals