Troubleshooting by Remote Controller Si20-701_B
453
Remote Controller Display
UF
Applicable Models
RZQ(S)-B/C
Method of Error Detection
Check the transmission between the indoor and outdoor
units with a micro-computer when the power turned ON.
Detect by checking the following temperature differences
during compressor operation.
A: Difference in temperature detected by the indoor
heat exchanger thermistor (R2T) and the indoor
suction air thermistor (R1T)
B: Difference in evaporation temperature (Te) (or
condensation temperature (Tc) during heating
operation) detected by the indoor heat exchanger
thermistor (R2T) and the compressor sensor
Error Decision Conditions
îš„ When the transmission wiring between the indoor and
outdoor units is incorrect
îš„ When the following conditions continue for 20 minutes
during compressor operation
A: R2T – R1T < 4ºC, and
B: R2T – Te (or Tc during heating operation) > 14ºC
(24ºC during heating operation)
Supposed Causes
îš„ Defective transmission wiring between the indoor and
outdoor units
îš„ Mismatching of wiring and piping
îš„ Refrigerant shortage
îš„ Clogged refrigerant piping system

Table of Contents

Other manuals for Daikin FUY71FJV1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FUY71FJV1 and is the answer not in the manual?

Daikin FUY71FJV1 Specifications

General IconGeneral
BrandDaikin
ModelFUY71FJV1
CategoryAir Conditioner
LanguageEnglish

Related product manuals