EasyManuals Logo

Daikin FUY71FJV1 User Manual

Daikin FUY71FJV1
501 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #92 background imageLoading...
Page #92 background image
Troubleshooting by Remote Controller Si20-701_B
85
Note:
If "A3" is detected by a PCB without X15A, the PCB is
defective.
Error
displayed again?
NO
YES
YES
Replace the float
switch.
Is the float
switch connected ?
NO
Connect the float
switch.
Replace the
indoor unit PCB.
Remove the float switch,
short circuit, and restart
operation.
A

Table of Contents

Other manuals for Daikin FUY71FJV1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FUY71FJV1 and is the answer not in the manual?

Daikin FUY71FJV1 Specifications

General IconGeneral
BrandDaikin
ModelFUY71FJV1
CategoryAir Conditioner
LanguageEnglish

Related product manuals