EasyManuals Logo

Daikin FUY71FJV1 User Manual

Daikin FUY71FJV1
501 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #95 background imageLoading...
Page #95 background image
Si20-701_B Troubleshooting by Remote Controller
88
Remote Controller Display
A6
Applicable Models
FCQ, FHQ, FAQ
Method of Error Detection
Detection of abnormal fan speed by signal from the fan
motor
Error Decision Conditions
The error is generated when the rotation speed of the fan
motor are not detected while the output voltage to the fan
is at its maximum.
For FCQ-C7, FAQ-BU
When fan speed does not increase
Supposed Causes
îš„ Defective indoor unit fan motor
îš„ Breaking or disconnection of wire
îš„ Defective contact
îš„ Defective indoor unit PCB
For FCQ-C7, FAQ-BU
îš„ Disconnection, short circuit or disengagement of
connector in fan motor harness
îš„ Defective fan motor (disconnection, poor insulation)
îš„ Abnormal signal from fan motor (defective circuit)
îš„ Defective Indoor unit PCB
îš„ Instantaneous fluctuation of power supply voltage
îš„ Fan motor lock
(Caused by motor or other external factors)
îš„ Fan does not turn due to a tangle of foreign matters.
îš„ The connector between the high-voltage PCB and the
low-voltage PCB is disconnected.

Table of Contents

Other manuals for Daikin FUY71FJV1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FUY71FJV1 and is the answer not in the manual?

Daikin FUY71FJV1 Specifications

General IconGeneral
BrandDaikin
ModelFUY71FJV1
CategoryAir Conditioner
LanguageEnglish

Related product manuals