TECHNICAL MANUAL4
1 MAIN FEATURES
PERFORMANCE AND COMPACTNESS IN RECESSED CEILING INSTALLATIONS
The range is completed by FWP-C, which uses inverter EC technology in the electric motors. To the features of FWP-C adds the ben-
ets of brushless technology, including a reduction in electricity consumption and consequent reduction in CO
2
emissions, increase
in operating exibility thanks to the modulation of air ow and increase in the level of comfort in terms of temperature, humidity
and noise levels.
The range is made up of 8 models with air ows from 300 to 1200 m³/h.
Continuous modulation of the air ow and the use of high-eciency heat exchangers enables operation also with small air-water
temperature dierences.
The heat exchangers can also be optimized in the circuit for centralized applications such as district cooling.
2 MAIN COMPONENTS
STRUCTURE
Built from galvanised steel sheet, heat and sound insulated by means of Class 1 self-extinguishing panels. Reduced height to facilitate
installation in a horizontal position in a false ceiling. The structure incorporates a drip tray and condensate drain outlet.
The main condensate drip tray is situated inside the structure of the unit and is at a positive pressure relative to the drain outlet to
facilitate condensate drainage.
HEAT EXCHANGER
High eciency standard with 3 rows, but also available with 4 rows upon request, heat exchanger made with copper piping and
aluminium ns blocked to pipings by mechanical expansion, provided with brass manifolds and air vent valve.The heat exchanger
usually comes with water connections mounted on the left, but it can be turned by 180°. High-eciency heat exchangers optimized
for district cooling applications are available on request.
FANS
Double suction centrifugal fans made with ABS or aluminium, with statically and dynamically balanced forward-curving blades,
directly coupled to the electric motor.
EC MOTOR
Single-phase asynchronous multi-speed electric motor with permanently connected capacitor and thermal protector, mounted on
vibration-damping supports.
AIR FILTER
Washable air lter, made of acrylic bre, ltration class G3, applied on the air intake; may be pulled out from below.
AIR INTAKE
Air intake from the front or bottom of the unit, according to system requirements.
INSTALLATION EXAMPLE
The bearing structure allows to combine a large range of accessories in suction and air delivery in order to obtain the optimized unit
conguration.