Operation Manual OM 1077-1
Group: Applied Air Systems
Part Number: OM 1077
Date: July 2016
Maverick
®
I Package Air Conditioner
DDC Rooftop Unit Controller
Heating & Cooling, Gas/Electric and Electric/Electric
Models MPS 003B – 025B
3 to 25 Tonns [10.6 to 87.9 kW]
R-410A Refrigerant

Other manuals for Daikin Maverick I

Questions and Answers

  • A
    Alexander CrossJul 25, 2025
    Why is my Daikin Air Conditioner not cooling enough?
    • D
      Deborah JonesJul 25, 2025
      Several factors can cause insufficient cooling in your Daikin Air Conditioner. It could be due to an improperly sized unit, requiring a load recalculation. Improper airflow, which should be around 400 CFM per ton, can also be a factor. Other potential causes include incorrect refrigerant charge (follow the procedure on the unit's service panel), air, non-condensables, or moisture in the system (recover refrigerant, evacuate and recharge, and add a filter drier), or incorrect voltage (voltage at compressor terminals must be within 10% of the rating plate volts when the unit is operating).
  • C
    Chelsea GillJul 30, 2025
    What to do if my Daikin Heat Pump unit will not run?
    • G
      gardnerjasmineJul 30, 2025
      If your Daikin Heat Pump unit won't run, there are several potential causes: * A power issue: check for correct voltage at the compressor contactor in the control box, or replace blown fuses. * Thermostat calibration: try resetting the thermostat if it's set too high. * Contactor failure: check for 24 volts at the contactor coil and replace it if the contacts are open. * Transformer issue: check the wiring and replace the transformer if it's defective. * High pressure control: reset it, noting that it opens at 450 PSIG. See also High Head Pressure Remedy. * Damaged low voltage wiring: replace the thermostat wiring.
  • J
    James RhodesAug 4, 2025
    How to fix a Daikin Air Conditioner when the condenser fan runs but the compressor doesn't?
    • R
      Robin RobertsAug 4, 2025
      If your Daikin Air Conditioner's condenser fan is running, but the compressor isn't, start by checking for loose connections and ensure the correct voltage at the compressor, tightening all connections. The compressor might be stuck, grounded, have an open motor winding, or an open internal overload; wait at least 2 hours for the overload to reset, and if it remains open, replace the compressor. A low voltage condition could also be the cause; at compressor terminals, voltage must be within 10% of rating plate volts when the unit is operating. Consider adding start kit components to address this.
  • M
    Matthew MilesAug 9, 2025
    Why is my Daikin Heat Pump providing insufficient cooling?
    • P
      Peter LaneAug 9, 2025
      Insufficient cooling in your Daikin Heat Pump can stem from several issues: * Incorrect unit size: recalculate the load to ensure the unit is appropriately sized. * Improper airflow: verify airflow is approximately 400 CFM per ton. * Refrigerant issues: charge the unit per the procedure attached to the service panel, or recover refrigerant to evacuate and recharge, adding a filter drier if there's air, non-condensables, or moisture in the system. * Voltage problems: ensure voltage at the compressor terminals is within 10% of the rating plate volts when the unit is operating.
  • A
    alexandra46Aug 14, 2025
    What to do if my Daikin Air Conditioner unit will not run?
    • E
      Erin FisherAug 14, 2025
      If your Daikin Air Conditioner unit isn't running, several issues could be the cause. Check for power issues or loose electrical connections, ensuring correct voltage at the compressor contactor in the control box. The thermostat might be out of calibration (reset it), or a contactor might have failed (check for 24 volts at the contactor coil and replace if contacts are open). Blown fuses (replace them), a defective transformer (check wiring and replace the transformer if needed), an open high-pressure control (reset it; the high-pressure control opens at 450 PSIG), or damaged interconnecting low voltage wiring (replace the thermostat wiring) could also be responsible.
  • J
    Jason SanchezAug 19, 2025
    What to do if the condenser fan runs, but the compressor doesn’t in my Daikin Heat Pump?
    • A
      Alexander SampsonAug 19, 2025
      If the condenser fan runs but the compressor doesn’t in your Daikin Heat Pump, consider these possibilities: * Loose connection: check for correct voltage at the compressor and tighten all connections. * Compressor issue: wait at least 2 hours for overload to reset. If still open, replace the compressor, as it may be stuck, grounded, have an open motor winding, or an open internal overload. * Low voltage: at compressor terminals, voltage must be within 10% of rating plate volts when unit is operating. You may need to add start kit components.

Summary

Introduction

Controller Component Locations

Diagram showing locations of controller components and connectors.

Safety and Warnings

Critical safety warnings for installation, service, and operation.

Control Inputs and Outputs

Control Inputs

List and descriptions of unit control inputs and their functions.

Control Outputs

List and descriptions of unit control outputs and their functions.

Control Input Descriptions

Detailed explanations for each control input, e.g., sensors, switches.

Control Output Descriptions

Detailed explanations for each control output, e.g., compressors, fans.

Unit Installation

Sequence of Operation

Cooling Sequence

Operation sequence for cooling demand, including staging.

Heating Sequence

Operation sequence for heating demand, including heat source priority.

Integrated Furnace Control (IFC)

IFC function, fault codes, and call for heat sequence.

Alarm List

Alarm and Diagnostic Codes

List of alarms, origin, description, and troubleshooting information.