www.DaikinApplied.com 43 OM 752-4
Conguration Parameter Name Abr. Notes Default
LUI
Menu
item
1
Economizer IA/OA Enthalpy Differential EED 1 .3 btu/lb (3 kJ/kg)
e6
External BI-3 Conguration 0 = Ventilation Lockout, 1 = Exhaust Interlock 0
B3
Filter Alarm Enable 0 = disable, 1 = enable 0
CE
Filter Change Hours Setpoint fan run hours between lter change alarms 700 hrs
ce
Primary Cool Proportional Band 18°F (10°C)
Primary Cool Integral Time 180 sec
Primary Heat Proportional Band 54°F (30°C)
Primary Heat Integral Time 300 sec
Discharge Air Temp Proportional Band 3.996°F (2.22°C)
Discharge Air Temp Integral Time 300 sec
CO
2
Proportional Band 100 PPM
CO
2
Integral Time 600 sec
Ventilation Cooling Low Limit Setpoint VCLL discharge air low limit during ventilation or economizer cooling 54°F (12°C)
d2
Discharge Air High Limit DAHL 125°F (51.7°C)
Space Fan Off Delay 4 min
Fan Cycling Conguration
space fan operation during occupied, standby and bypass occupancy modes: 2 =
continuous, 3 = cycle
2
cf
Space Fan Speed Changes Per Hour
example: 6/60min = 10 min (maximum of 1 fan speed change every 10 min when
fan in auto)
6
Space Fan Run Time Reset reset total run time: 1 = reset (you must return the variable back to 0 after reset) 0
Space Humidity Sensor Enable
0 = disable, 1 = enable (this variable will be factory set to 1 when the unit is
ordered with optional humidity sensor)
0
Outdoor Humidity Sensor Enable
0 = disable, 1 = enable (this variable will be factory set to 1 when the unit is
ordered with optional humidity sensor)
0
OAD Stroke Time 90 sec
Application Name and Version Label
1. Indicates parameters accessible through the keypad/display.
2. Requires optional equipment.
dIaGnostICs and serVICe