OPTIONAL fEATURES
MICROTECH 2300 UNIT CONTROLLERDAIKIN APPLIED
16
Items Required
• Model SD, SN, ST, SL = 3 stage thermostat
• Model SC, SM, SS, SH, SR = 2 stage thermostat
• Return air sensor
NOTICE
This feature is not available if unit is controlled by a wall sensor.
Unit Control Settings
• MT2310 I/O Expansion Module Jumper Settings:
— SW7 = ON (HGR Enabled)
— SW8 = OFF (WSE Disable)
Operation
Unit will run at maximum compressor capacity with low CFM to
maximize latent capacity.
Example: A 2-stage unit size 028, wired for Simplied
Dehumidication:
• Upon a call for Y1, and the return air temperature is 68°F or
greater. TB1-3, HST on the MT2310 I/O expansion board
will be energized, allowing the compressor to operate at full
load and the fan to operate at 600 CFM.
• Upon a call for Y2, Y1 on the unit control board will be
energized, allowing the compressor to operate at part load
and the fan to operate at 700 CFM. (Factory default fan
speed setting 3)
• Upon a call for Y3, Y2 on the unit control board will be
energized, allowing the compressor to operate at full load
and the fan to operate at 800 CFM. (Factory default fan
speed setting 3)
Hot Gas Reheat Smart Dehumidication
Application
By utilizing the factory installed hot gas reheat and smart air ow
management; dehumidication can be achieved in applications
where precise humidity control is required.
Items Required
• Unit with Hot Gas Reheat option
• Humidistat and a Thermostat OR Digitally Adjustable Wall
Sensor
• Return air sensor
Unit Control Settings
• MT2310 I/O Expansion Module Jumper Settings:
— SW7= ON (HGR Enabled)
— SW8 = OFF (WSE Disabled)
Operation
A call for heating or cooling has a higher priority than a call for
dehumidication. Dehumidication is allowed only if the room
temperature is satised and the return air temperature is 68°F or
greater. If the controller detects the need for heating or cooling,
or if the Humidistat is no longer calling for dehumidication,
dehumidication mode will be suspended. Dehumidication
mode will enable the 3-way hot gas bypass valve, sending hot
superheated refrigerant to the hot gas reheat coil while running
the compressor at full load and the fan at dehumidication speed.
NOTICE
See Fan Performance section in catalog for unit size specic fan speeds.
Humidistat Controlled Dehumidication
Application
Similar to the simplied dehumidication option, this option also
maximizes latent capacity by using a humidistat and thermostat.
This option allows the room thermostat to control sensible
cooling, while the independent humidistat controls room humidity
levels
Items Required
• Humidistat combined with a...
• Model SD, SN, ST, SL = 3 stage thermostat
• Model SC, SM, SS, SH, SR = 2 stage thermostat
• Return air sensor
NOTE: This feature is not available if unit is controlled by wall
sensor
Unit Control Settings
• MT2310 I/O Expansion Module Jumper Settings:
— SW7 = ON (HGR Enabled)
— SW8 = OFF (WSE Disabled)
Operation
• A call for heating or cooling has a higher priority than a call
for dehumidication. Dehumidication is allowed only if the
room temperature is satised and the return air temperature
is 68°F or greater.
• If the controller detects the need for heating or cooling, or
if the Humidistat is no longer calling for dehumidication,
dehumidication mode will be suspended.
• Dehumidication mode will enable the 3-way hot gas
bypass valve, sending hot superheated refrigerant to the
hot gas reheat coil while running the compressor at full load
and the fan at dehumidication speed.
NOTICE
See Fan Performance section in catalog for unit size specic fan speeds.
Dehumidication Only
Application
In applications where only dehumidication is needed, the
humidistat can be wired to HST on the MT2300 unit controller,
allowing the WSHP unit to operate in dehumidication mode only.
The unit will only respond to a call for dehumidication whenever
the return air temperature is 68°F or greater.