OPTIONAL fEATURES
Items Required
Humidistat
Return air sensor
Unit Control Settings
I/O Expansion Module Jumper Settings:
SW7 = ON (HGR Enabled)
SW8 = OFF (WSE Disabled)
Operation
Upon a call for dehumidication, the unit will run in Cool Stage 2
compressor capacity and Dehumidication fan speed.
Example
A 2-compressor model SL, unit size 072, wired for
Dehumidication Only:
Upon a call for dehumidication from the humidistat, HST
on the unit control board will be energized, allowing both
compressors to operate at full load and the fan to operate at
dehumidication CFM.
A 2-stage model SD, unit size 026, wired for Dehumidication
Only:
Upon a call for dehumidication from the humidistat, HST
on the unit control board will be energized, allowing the
compressor to operate at full load and the fan to operate at
dehumidication CFM.
NOTICE
See Fan Performance section in catalog for unit size specic fan speeds.
Analog Humidity Sensor Input
Any of the dehumidication options described can also be
used with an optional 0-10VDC relative humidity sensor.
An analog humidity sensor is intended to be an option for
units with BACnet communications to allow the relative
humidity value to be viewed and the dehumidication
setpoint to be adjusted via network communications.
When an analog humidity sensor is used, and optional
Humidity Senor Failure alarm can be congured to indicate
if the sensor reading has become unreliable. The Sensor
Failure Alarm feature is disabled by default, and can be
activated via network communications.
While an analog humidity sensor can be used on units
without network communications, there will be no way to the
relative humidity or adjust the relative humidity setpoint, so
a humidistat is recommended.
Waterside Economizer
Application:
The MT2300 controls the waterside economizer. Upon a call
for economizer operation via TB1-3, HST on the MT2310 I/O
expansion board, for units without hot gas reheat or Y1 on the
MT2300 baseboard for units with hot gas reheat), the output
to the 3-way diverting valve and the fan motor are energized,
allowing water ow through the economizer coil and fan
operation.
Items Required
Multi-stage thermostat or sensor
Unit Control Settings
MT2310 I/O Expansion Module Jumper Settings:
SW8 = ON (WSE Enable)