27
OM 1364-1
WWW.DAIKINAPPLIED.COM
A2L DETECTION AND MITIgATION
GID id Name Min Limit Max Limit Default Description
43 Sensor 4 State 1 65535 0 Sensor 4 current state. Value = 2, then state is "run"
44 Sensor 4 Faults 0 65535 0 Sensor 4 internal faults reported. For instance value = 0, then no faults.
45 Sensor 4 Temperature -400 940 0 Sensor 4 Temperature reported value. For instance value = 250, then Temp = 25 C
46 Sensor 4 Humidity 0 1000 0 Sensor 4 Humidity reported value. For instance value = 400, then Humidity = 40%
47 Sensor 4 Pressure 0 4000 0 Sensor 4 Pressure reported value. Not available for now.
48 Sensor 5 Address GID14 GID14 + 7 0 Sensor 5 Address
49 Sensor 5 Level 0 65535 0 Sensor 5 LFL reported value. For instance value = 200, then LFL is 20%
50 Sensor 5 State 1 65535 0 Sensor 5 current state. Value = 2, then state is "run"
51 Sensor 5 Faults 0 65535 0 Sensor 5 internal faults reported. For instance value = 0, then no faults.
52 Sensor 5 Temperature -400 940 0 Sensor 5 Temperature reported value. For instance value = 250, then Temp = 25 C
53 Sensor 5 Humidity 0 1000 0 Sensor 5 Humidity reported value. For instance value = 400, then Humidity = 40%
54 Sensor 5 Pressure 0 4000 0 Sensor 5 Pressure reported value. Not available for now.
55 Sensor 6 Address GID14 GID14 + 7 0 Sensor 6 Address
56 Sensor 6 Level 0 65535 0 Sensor 6 LFL reported value. For instance value = 200, then LFL is 20%
57 Sensor 6 State 1 65535 0 Sensor 6 current state. Value = 2, then state is "run"
58 Sensor 6 Faults 0 65535 0 Sensor 6 internal faults reported. For instance value = 0, then no faults.
59 Sensor 6 Temperature -400 940 0 Sensor 6 Temperature reported value. For instance value = 250, then Temp = 25 C
60 Sensor 6 Humidity 0 1000 0 Sensor 6 Humidity reported value. For instance value = 400, then Humidity = 40%
61 Sensor 6 Pressure 0 4000 0 Sensor 6 Pressure reported value. Not available for now.
62 Sensor 7 Address GID14 GID14 + 7 0 Sensor 7 Address
63 Sensor 7 Level 0 65535 0 Sensor 7 LFL reported value. For instance value = 200, then LFL is 20%
64 Sensor 7 State 1 65535 0 Sensor 7 current state. Value = 2, then state is "run"
65 Sensor 7 Faults 0 65535 0 Sensor 7 internal faults reported. For instance value = 0, then no faults.
66 Sensor 7 Temperature -400 940 0 Sensor 7 Temperature reported value. For instance value = 250, then Temp = 25 C
67 Sensor 7 Humidity 0 1000 0 Sensor 7 Humidity reported value. For instance value = 400, then Humidity = 40%
68 Sensor 7 Pressure 0 4000 0 Sensor 7 Pressure reported value. Not available for now.
69 Sensor 8 Address GID14 GID14 + 7 0 Sensor 8 Address
70 Sensor 8 Level 0 65535 0 Sensor 8 LFL reported value. For instance value = 200, then LFL is 20%
71 Sensor 8 State 1 65535 0 Sensor 8 current state. Value = 2, then state is "run"
72 Sensor 8 Faults 0 65535 0 Sensor 8 internal faults reported. For instance value = 0, then no faults.
73 Sensor 8 Temperature -400 940 0 Sensor 8 Temperature reported value. For instance value = 250, then Temp = 25 C
74 Sensor 8 Humidity 0 1000 0 Sensor 8 Humidity reported value. For instance value = 400, then Humidity = 40%
75 Sensor 8 Pressure 0 4000 0 Sensor 8 Pressure reported value. Not available for now.
76 DF Saving Time 15 120 15
Data Flash saving time in minutes. How frequent data is saved on non volatile
memory.
77
Nominated Sensor
Addr
48 55 55 Sensor address to be reset to the default value
78
Sensor Reset
Command
0 1 0 Command to invoke sensor function reset, value = 1 then this command is invoked.
79
Sen Func Reset
Result
0 1 0
Final result of the sensor reset function operation. Value = 0, the operation was
successful.