Adjust Filter1? Set Flow Buff? Set Altitude Set Out2 Type?
3
Set Out2?
*ALT=0FT ↑
1
ALT=0 ↓↑
OUT2 TYPE=TEMP↓
1
OUT2 TYP=TEMP↓↑
3
OUT2=0-10V ↓
OUT2 TYPE=ALRM ↑
BUFF SIZE=30 ↓↑
1
FLOW BUFF=30 ↓↑
FILTER1=0 ↑
1
FILTER1=0 ↓↑
3
OUT2=0-5V ↓↑
3
OUT2=4-20mA
1
OUT2=4-20mA ↓↑
Adjust dampening lter value
from 0 (OFF) to 99%.
Set the altitude for ow correction
from 0 to 18,000 ft.
Set the number of ow
calculations to be averaged:
1 to 1,000.
Sets OUT2 to produce
Temperature output.
Sets OUT2 to produce
Alarm output.
In addition, “SW2” must be set
to the VDC position to change
airow output to 0–10VDC.
In addition, “SW2” must be set
to the VDC position to change
airow output to 0–5VDC.
In addition, “SW2” must be set to
the mA position to change airow
output to 4–20mA.
1. Factory default/current setting
2. If a selection is made that requires SW1 to be set, the LCD displays “Set
SW1 on Board”.
3. If a selection is made that requires SW2 to be set, the LCD displays “Set
SW2 on Board”.