ESIE17-08 | Part 5. Appendix 5.3. Wiring diagram
R32 Sky-Air RZAG-M
Page 122 15/11/18 | Version 1.1
Figure 5-4: Wiring diagram - outdoor unit RZAG71MV1, RZASG100MV1, AZAS100MV1
Notes
1. Refer to the wiring diagram sticker (on the back of the front plate) for how to use the BSI~BS3 and DS1 switches.
2. When operating, do not short-circuit protection device(s) S1PH, S1PL and Q1E.
3. Refer to the combination table and the option manual for how to connect the wiring to X6A, X28A and X77A.
4. Colours: BLK: Black, RED: Red, BLU: Blue, WHT: White, GRN: Green.
5. Windings: L-N: 2 - Earth: 1
Legend
A1P Printed circuit board (main) R6T Thermistor (liquid)
BS1~3 (A1P) Push-button switch R7T Thermistor (fin)
DS1 (A1P) Dipswitch R8 (A1P) Resistor
E1~3 (A1P) Connector S1PH High pressure switch
E1H * Bottom plate heater S1PL Low pressure switch
F1U (A1P) Fuse T 31,5 A 250 V SEG1~3 (A1P) 7-segment display
F2U (A1P) Fuse T 6,3 A 250 V TC1 (A1P) Signal transceiver circuit
F3U (A1P) Fuse T 6,3 A 250 V U, V, W (A1P) Connector
F6U (A1P) Fuse T 5 A 250 V V1D (A1P) Diode
F8~9U * Fuse F 1 A 250 V V*R (A1P) Diode module
HAP (A1P) Light-emitting diode (service monitor is green) X1M Terminal strip
K1R (A1P) Magnetic relay (Y1S) Y1E, Y3E Electronic expansion valve
K2R (A1P) Magnetic relay (Y2S) Y1~2S Solenoid valve (4-way valve)
K4R (A1P) Magnetic relay (E1H) Z*C Noise filter (Ferrite core)
K13R~K15R,
K10R (A1P)
Magnetic relay Z*F (A1P) Noise filter
K11M (A1P) Magnetic contactor * Optional
L (A1P) Connector # Field supply
M1C Compressor motor
M1F Fan motor
Symbols
N (A1P) Connector Connection
PFC (A1P) Power factor correction X1M Main terminal
PS (A1P) Switching power supply Earth wiring
Q1DI Earth leakage circuit breaker (30mA) Field supply
Q1E Overload protection Option
R1T Thermistor (air) Switch box
R2T Thermistor (discharge) PCB
R3T Thermistor (suction) Wiring depending on model
R4T Thermistor (heat exchanger) Protective earth
R5T Thermistor (heat exchanger middle) Field wire
RZAG71MV1, RZASG100MV1, AZAS100MV1
OUTDOOR
Layout
N = note 5
INDOOR
Position of compressor terminal
SEE NOTE 3
Upper EEV
Lower EEV
SEE
NOTE 3
SEE NOTE 3
4D109936