EasyManua.ls Logo

Daikin R35CV1A - Electrical Box Temperature Rise

Daikin R35CV1A
212 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Si01-406 Troubleshooting
Service Diagnosis 107
4.15 Electrical Box Temperature Rise (L3)
Remote
Controller
Display
L3
Method of
Malfunction
Detection
An electrical box temperature rise is detected by checking the radiation fin thermistor with the
compressor off.
Malfunction
Decision
Conditions
With the compressor off, the radiation fin temperature is above 122°C. (Reset is made when the
temperature drops below 113°C.)
Supposed
Causes
Fin temperature rise due to defective outdoor unit fan
Fin temperature rise due to short-circuit
Fin thermistor defective
Connector in poor contact
Outdoor unit PCB defective

Table of Contents

Other manuals for Daikin R35CV1A

Related product manuals