5 Installation
Installation and operation manual
17
REYQ8~20+REMQ5T7Y1B
VRV IV system air conditioner
4P353996-1E – 2018.04
Pre-charging refrigerant
Step 1
Calculate additional refrigerant charge amount: R (kg)
Refrigerant overcharge happened, recover
refrigerant to reach R=Q
Step 2+3
Close valves C, D and A
Open valve B to the liquid line
Execute pre-charging amount: Q (kg)
Disconnect the manifold from the gas line and the high pressure/low
pressure gas line
Step 4a
Close valve B
Charging is finished
Fill in the amount on the additional
refrigerant charge label
Input the additional refrigerant amount via
setting [2-14]
Go to test run
Step 4b
Close valve B
R=Q R>QR<Q
Continued on next page >>
p
<
p
>
R410AN2
C D
A B
Charging refrigerant
Step 6
Proceed with automatic or manual charge
Step 6b
Activate field setting [2-20]=1
Unit will start manual refrigerant charging operation.
Step 6a
Push 1x BS2: "888"
Push BS2 for more than 5 seconds "t01" pressure equalisation
Open valve A
Charge remaining amount of refrigerant P (kg)
R=Q+P
Depending on ambient conditions, the unit will decide to perform autocharge
operation in heating or cooling mode.
Close valve A
Push BS3 to stop manual charging
Charging is finished
Fill in the amount on the additional refrigerant charge label
Input the additional refrigerant amount via setting [2-14]
Go to test run
Step 5
Connect valve A to the refrigerant charge port (d)
Open all outdoor unit stop valves
R>Q
Automatic charge
Manual charge