EasyManua.ls Logo

Daikin RoCon BF - Lambda-Gx Level (Only for the Heat Generator GCU Compact); Rotary Switch Setting: DHW Reheating

Daikin RoCon BF
64 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Operating instructions
44
Daikin RoCon
Daikin Control unit
008.1543999_00 – 03/2017 – EN
6 x Parameter settings
6.2.6 "Lambda-Gx" level (only for the heat generator GCU compact)
This parameter level is not displayed if the "Standby" operating mode is active.
6.3 Rotary switch setting: DHW Reheating
Parameter Name Access Setting range
Min / Max
Factory
setting
Incre-
ment
BE HF
Gas type Changeover natural gas/liquid gas. For this, please observe the mechanical switchover of the
gas valve (see installation and maintenance instructions of the GCU compact).
N E Natural gas
Liquid gas
Natural gas -
Corr qGas start Correction value of the amount of gas for the ignition process. This value can be adjusted in
the case of starting problems.
N E -10 - 20 % 0 1 %
100% Calibration Off: No function
On: Manual start of the calibration. It is always necessary for a burner change or if the ionisa-
tion electrode is cleaned or replaced. The firing unit determines the new ionisation base value
by this. It takes approx. 30 - 60
s. Afterwards, the parameter value is automatically set to "Off".
N E Off
On
Off -
Corr power start Adjustment of the start power. This enables noise and start problems to be counteracted. N E -16 - 14 % 0 2 %
CL - Offset CES Adjustment of the presetting of the GAS control valve. Value only works once until the next ad-
aptation, it is then independently changed/adjusted by the controller. Adjustment can be nec-
essary if the gas fitting is being replaced and too little gas would flow into the combustion
chamber from the control valve.
N E 20 - 40 % xx.x 0.2 %
BCCRe-Update Status message, informative N E Off
On
Off -
Error Code Active error of the firing unit (see tab. 7-2). N S 0 0 -
Q-SetpointRoCon Informative - Variable process value. N S - xxx -
Q-ActualValueRo-
Con
Informative - Variable process value. N S - xxx -
T-HS Current T-HS. N S - xxx -
T-Return Current T-Return. N S - xxx -
IO-SP Informative - Variable process value. N S - xxx -
IO-AV Informative - Variable process value. N S - xxx -
ConV Informative - Variable process value. N S - xxx -
ConF Informative - Variable process value. N S - xxx -
IO-BV Informative - Variable process value. N S - xxx -
IO-CalMax Informative - Variable process value. N S - xxx -
IO-Comp Informative - Variable process value. N S - xxx -
IO-S Informative - Variable process value. N S - xxx -
FI-T Informative - Variable process value. N S - xxx -
IgtoCal Number of necessary ignitions until calibration is automatically carried out. N S - xxx -
Lerr Last error of the firing unit (see tab. 7-2). N S - xxx -
PLErr Count of how often the last error has occurred. N S - xxx -
Burner Starts Sum of all starts that are stored in the firing unit of the heat generator. N S - - 1
Burner Oper Time Overall runtime of the burner in hours, which is stored in the firing unit of the heat generator. N S - - 1 h
Tab. 6-6 Parameters in the "Configuration" rotary switch setting, "Lambda-Gx" level
Parameter Description Access Setting range
Min / Max
Factory
setting
Incre-
ment
BE HF
1x Hot Water Start of a one-time hot water generation to the set target value [T-DHW Setpoint 1] without time
limit, independent of the heating programs.
E E Off
On
Off -
DHW Reloadtime Setting limits the period of time for hot water generation to the set target value [T-DHW Setpoint
1]. After the period of time has elapsed, the control unit switches back to the previously active
operating mode. Hot water generation is carried out to the then current target value.
E E 0 - 240 min 0 min 1 min
Tab. 6-7 Parameters in the "DHW Reheating" rotary switch setting

Table of Contents

Related product manuals