7 x Errors and faults
Daikin RoCon
Daikin Control unit
008.1543999_00 – 03/2017 – EN
Operating instructions
57
For further information on possible errors and faults, see appli-
cable documents.
Code Component/Designation Error Possible error rectification
E72 Internal mixer sensor t
V2
Measured value outside measuring range,
temperature sensor defective.
Check cable, terminal and plug connec-
tions.
Replace temperature sensor.
E75
External temperature sen-
sor
E76
Storage tank temperature
sensor
E81 EEPROM
Internal error.
Total reset
Replace control unit switching panel
PCB.
E88
Control unit switching panel
PCB
E91 Connected CAN modules CAN module bus ID duplicated. Configure bus addresses correctly.
E100
(1
Flue gas temperature sen-
sor
Measured value outside measuring range,
sensor/temperature sensor defective.
(1 locking error if the flue gas temperature sensor is ob-
ligatory for this heat generator type (e.g. Daikin A1).
Burner release only takes place if the fault has been
manually unlocked.
Check cable, terminal and plug connec-
tions.
Replace sensor/temperature sensor.
E128
Temperature sensor in the
flow sensor
Measured value outside measuring range,
sensor/temperature sensor defective.
Check cable, terminal and plug connec-
tions.
Replace sensor/temperature sensor.
E129 Pressure sensor
E198 Flow sensor Volume flow too low.
Check heating circulation
pump/filter/heating network.
E200 Communication, firing unit
Communication interrupted between firing
unit and control unit switching panel PCB.
Check cable and plug connections.
Total reset
Replace control unit switching panel
PCB.
Replace the firing unit.
W8001
Flow sensor
Warning message: Measured value less than
recommended minimum flow.
Check parameter settings (see tab. 6-2).
Check pipes and valves for blockages.
Check integrated heating circulation
pump.
E8002
Measured value under permitted minimum
value. Flow sensor/integrated heating circula-
tion pump defective.
W8003
Flue gas temperature
Warning message: The flue gas temperature
has exceeded the limit temperature.
Clean the boiler.
Check flue gas temperature sensor.
E8004
Flue temperature has exceeded the permissi-
ble absolute maximum value.
E8005
Water pressure
Measured value under permissible minimum
value.
Top up heating water.
Leak test.
W8006
Warning message: Maximum permissible
pressure drop exceeded.
W8007
Warning message: Measured value exceeds
permissible maximum value.
Check diaphragm expansion vessel.
Drain heating water.
Tab. 7-3 Error codes (can be detected by the switching panel PCB)
Observe maximum tightening torque of 10 Nm for all
temperature sensors.