Appendix SiEN34-705
212 General Information
7.15.5 [Malfunction of Transmission Examples]
Faulty Condition Caused by Branch Lines.
Applicable
Models
VRV in general
Condition A transmission malfunction occurred when the centralized controller was added to the existing
system.
Cause Ten of all indoor-to-outdoor lines were branch lines from a single bus cable.
Measure Corrected IN - OUT wiring to one - after another wiring
Point of
Diagnosis