2 | Components
Service manual
113
FTXF20~71A + FTXF20~25B + FTXF20~42C + ATXF20~71A + ATXF20~42C
+ RXF20~71A + RXF20~60B + RXF20~42C + ARXF20~71A + ARXF20~42C
Split Sensira R32
ESIE18-12E – 2021.02
a L803
b L804
c Measuring point
d Measuring point
e Measuring point
Is the resistance measurement correct? Action
Yes Proceed with the next step.
No Replace the reactor, see "2.11.2Repair
procedures"[4114].
4 Measure the inductance of the reactor using an LCR meter.
Result: The inductance MUST be as follows:
Measuring points Resistance
c‑d 88.5~101.5µH
a L803
b L804
c Measuring point
d Measuring point
Is the inductance measurement
correct?
Action
Yes Return to the troubleshooting of the
specific error and continue with the
next step.
No Replace the reactor, see "2.11.2Repair
procedures"[4114].