2 | Components
Service manual
38
FTXF20~71A + FTXF20~25B + FTXF20~42C + ATXF20~71A + ATXF20~42C
+ RXF20~71A + RXF20~60B + RXF20~42C + ARXF20~71A + ARXF20~42C
Split Sensira R32
ESIE18-12E – 2021.02
Is the measured value correct? Action
No Replace the 4‑way valve coil, see
"2.1.2Repair procedures"[441].
When outdoor temperature is mild and unit can switch between heating and
cooling
INFORMATION
This procedure is ONLY possible when the outdoor temperature is within the
temperature range for both Heating and Cooling operation mode. See the
databook on Business Portal for the temperature range of the operation modes.
3 Connect the 4‑way valve connector to the appropriate PCB.
4 Turn ON the power using the respective circuit breaker.
5 Activate Heating operation via the user interface.
6 With the 4‑way valve connector connected to the PCB, measure the voltage
on the 4‑way valve connection of the PCB.
Result: The measured voltage MUST be:
Class Voltage
Class 20~42 12VDC
Class 50~71 220~240VAC
7 De-activate Heating and activate Cooling operation via the user interface.
8 Measure the voltage on the 4‑way valve connection on the PCB.
Result: The measured voltage MUST be:
Class Voltage
Class 20~42 0VDC
Class 50~71 0VAC
Are the measured voltages correct? Action
Yes Perform a position check of the 4-way
valve, see "2.1.1Checking
procedures"[437].
No Perform a check the main PCB, see
"2.8Main PCB"[474].
When outdoor temperature does not allow the unit to run in cooling or heating
mode
INFORMATION
Follow this procedure when the outdoor temperature is outside the temperature
range for one of the operation modes (Heating or Cooling). The unit CANNOT
operate in the mode for which the outdoor temperature is outside its temperature
range. See the databook on Business Portal for the temperature range of the
operation modes.
9 Connect the 4‑way valve connector to the appropriate PCB.
10 Turn ON the power using the respective circuit breaker.
11 With the unit operating, connect the service monitoring tool to the unit and
check whether the unit is operating in Heating or Cooling mode.