EasyManua.ls Logo

Daikin Sensira Series - Page 43

Daikin Sensira Series
172 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 | Components
Service manual
43
FTXF20~71A + FTXF20~25B + FTXF20~42C + ATXF20~71A + ATXF20~42C
+ RXF20~71A + RXF20~60B + RXF20~42C + ARXF20~71A + ARXF20~42C
Split Sensira R32
ESIE18-12E – 2021.02
cd a b a
a 4‑way valve pipe
b 4‑way valve
c Putty
d Insulation
6 Install the putty (if available) and the insulation (if available) in their original
location.
7 Install the 4‑way valve coil on the 4‑way valve body, see "2.1.2 Repair
procedures"[441].
8 Add refrigerant to the refrigerant circuit, see "3.2.2 Repair
procedures"[4133].
To install the 4-way valve coil
1 Install the 4‑way valve coil on the 4‑way valve body.
c a b
a Screw
b 4‑way valve coil
c 4‑way valve body
2 Install and tighten the screw to fix the 4‑way valve coil.
3 Route the 4‑way valve coil harness towards the appropriate PCB.
4 Connect the 4‑way valve coil connector to the PCB.
WARNING
When reconnecting a connector to the PCB, make sure to connect it on the correct
location and do NOT apply force, as this may damage the connector or connector
pins of the PCB.
5 Fix the 4‑way valve coil harness using new tie straps.
Is the problem solved? Action
Yes No further actions required.