Compressor motor winding
measurements are correct?
Action
Yes Continue with the next step.
No Replace the compressor, see
"2.2.2Repair procedures"[449].
5 Measure the continuity of the U, V and W wires between the compressor and
the PCB. If no continuity, correct as needed, see "5.2Wiring diagram"[4142].
6 Connect the Faston connectors to the compressor wire terminals U, V and W
U Wire terminal U
V Wire terminal V
W Wire terminal W
7 Install the compressor insulation.
8 Turn ON the power using the respective circuit breaker.
9 Start the unit operation via the user interface.
10 Wait for – or create condition to operate the compressor.
11 Once the compressor operates, measure the U-V-W inverter voltages. All
measurements MUST be the same.
Inverter voltage measurements are
correct?
Action
Yes Continue with the next step.
No Perform a check of the appropriate PCB,
see "2Components"[437].
12 Measure the current in each phase U, V and W while compressor is operating.
All measurements MUST be the same.
Compressor motor winding current
measurements are correct?
Action
Yes Perform an insulation check of the
compressor, see "2.2.1Checking
procedures"[444].
No Preventively replace the compressor,
see "2.2.2Repair procedures"[449].