Loading...
2 | Components
Service manual
51
FTXF20~71A + FTXF20~25B + FTXF20~42C + ATXF20~71A + ATXF20~42C
+ RXF20~71A + RXF20~60B + RXF20~42C + ARXF20~71A + ARXF20~42C
Split Sensira R32
ESIE18-12E – 2021.02
a
a
b
c
c
c
a
a Nut
b Compressor
c Damper
9 Remove the 3 dampers from the compressor.
INFORMATION
The compressor dampers may look different.
10 Remove the bushings and keep them for re-use.
11 To install the compressor, see "2.2.2Repair procedures"[449].
To install the compressor
1 Check the state of the dampers. Replace if worn.
2 Install the 3 dampers in the correct location on the unit.
a
a
b
c
c
c
a
a Nut
b Compressor
c Damper
INFORMATION
The compressor dampers may look different.
3 Remove the caps from the compression pipe and suction pipe.
CAUTION
The oil in the compressor is hygroscopic. Therefore remove the caps from the
compressor pipes as late as possible.