EasyManua.ls Logo

Daikin Sensira Series - Page 58

Daikin Sensira Series
172 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 | Components
Service manual
58
FTXF20~71A + FTXF20~25B + FTXF20~42C + ATXF20~71A + ATXF20~42C
+ RXF20~71A + RXF20~60B + RXF20~42C + ARXF20~71A + ARXF20~42C
Split Sensira R32
ESIE18-12E – 2021.02
1 Remove the expansion valve motor, see "2.3.2Repair procedures"[456].
2 Remove the putty. Keep for re-use.
a b c
a Putty
b Expansion valve pipe
c Expansion valve body
a b
a Expansion valve pipe
b Expansion valve body
INFORMATION
The expansion valve and motor can have a different configuration / layout.
3 Cut the expansion valve pipes using a pipe cutter.
4 Remove the expansion valve body.
5 Supply nitrogen to the refrigerant circuit. The nitrogen pressure MUST NOT
exceed 0.02MPa.
6 Heat the ends of the expansion valve pipes using an oxygen acetylene torch
and remove the expansion valve pipe ends.
7 Stop the nitrogen supply when the piping has cooled down.
8 To install the expansion valve body, see "2.3.2Repair procedures"[456].
To install the expansion valve body
1 Install the expansion valve body in the correct location and correctly oriented.
2 Supply nitrogen to the refrigerant circuit. The nitrogen pressure MUST NOT
exceed 0.02MPa.