2 | Components
Service manual
60
FTXF20~71A + FTXF20~25B + FTXF20~42C + ATXF20~71A + ATXF20~42C
+ RXF20~71A + RXF20~60B + RXF20~42C + ARXF20~71A + ARXF20~42C
Split Sensira R32
ESIE18-12E – 2021.02
To install the expansion valve motor with clip
1 Install the expansion valve motor on the expansion valve body.
INFORMATION
The expansion valve motor is equipped with a pipe retention clip. Install the pipe
retention clip over the pipe to lock the expansion valve motor.
b
a
c
a Expansion valve motor
b Pipe retention clip
c Pipe
2 Route the expansion valve motor harness towards the appropriate PCB.
3 Connect the expansion valve motor connector to the appropriate PCB.
WARNING
When reconnecting a connector to the PCB, make sure to connect it on the correct
location and do NOT apply force, as this may damage the connector or connector
pins of the PCB.
4 Fix the expansion valve motor harness using new tie straps.
5 Install the insulation cap on the expansion valve motor (if applicable).
Is the problem solved? Action
Yes No further actions required.
No Return to "2.3.1Checking
procedures"[453] of the expansion
valve and continue with the next
procedure.
To install the expansion valve motor with bracket
1 Install the expansion valve motor on the expansion valve body.
INFORMATION
The expansion valve motor is equipped with a metal bracket. Fit the nipples of the
metal bracket into the notches of the expansion valve body.
CAUTION
Make sure to install the expansion valve motor in the correct position (orientation).