2 | Components
Service manual
66
FTXF20~71A + FTXF20~25B + FTXF20~42C + ATXF20~71A + ATXF20~42C
+ RXF20~71A + RXF20~60B + RXF20~42C + ARXF20~71A + ARXF20~42C
Split Sensira R32
ESIE18-12E – 2021.02
Prerequisite: Turn OFF the respective circuit breaker.
Prerequisite: Remove the required plate work, see "2.10Plate work"[4101].
1 Remove the switch box, see "2.10Plate work"[4101].
2 Click the indoor unit fan motor cover out of the indoor unit. If needed, remove
the screw (if installed) on the right hand side of the fan motor cover for easier
removal.
a
a Indoor unit fan motor cover
3 Remove the rubber from the indoor unit.
4 Remove the indoor unit fan motor from the indoor unit.
5 To install the indoor unit fan motor, see "2.5.2Repair procedures"[465].
To install the DC fan motor assembly
1 Install the indoor unit fan motor in its correct location on the fan.
2 Install the rubber in front of the fan motor.
3 Click the indoor unit fan motor cover on the indoor unit. If removed, install
and tighten the screw on the right hand side of the fan motor cover.
a
a Indoor unit fan motor cover
4 Install the switch box, see "2.10Plate work"[4101].
Is the problem solved? Action
Yes No further actions required.