2 | Components
Service manual
91
FTXF20~71A + FTXF20~25B + FTXF20~42C + ATXF20~71A + ATXF20~42C
+ RXF20~71A + RXF20~60B + RXF20~42C + ARXF20~71A + ARXF20~42C
Split Sensira R32
ESIE18-12E – 2021.02
j j
k
f
g
abdc e
h h
i
j
j
j
j
j
a Power supply wires from X1M
b Ferrite core (power supply wires)
c Tie strap (power supply wires)
d Screw (ground wiring)
e Ferrite core (ground wiring)
f Connector X12A
g Compressor connector
h Tie strap (compressor harness)
i Ferrite core (compressor harness)
j Screw
k Main PCB
3 Install and tighten the screws.
4 Route the compressor harness through the ferrite core and connect the
compressor connector.
5 Install new tie straps to fix the compressor harness to the switch box.
6 Route the ground wire through the ferrite core. Install the ground wiring on
the switch box and fix using the screw.
7 If applicable: Connect the connector X12A.
8 Route the power supply wiring through the ferrite core and connect it to the
main power supply terminal X1M.
9 Fix the power supply wiring to the switch box using a new tie strap.
10 Connect all other connectors to the main PCB.
INFORMATION
Use the wiring diagram and connection diagram for correct installation of the
connectors, see "5.2Wiring diagram"[4142].
Is the problem solved? Action
Yes No further actions required.
No Return to "Checking procedures"[484]
of the PCB and continue with the next
procedure.