SiBE18-821_C Field Settings
Test Operation and Field Settings 149
Detailed Setting Procedure of Low Noise Operation and Demand Control
1. Setting mode 1 (H1P off)
(1) In setting mode 2, push the BS1 (MODE button) one time.
Setting mode 1 is entered and
H1P off.
During the setting mode 1 is displayed, “In low noise operation” and “In demand control” are
displayed.
2. Setting mode 2 (H1P on)
(1) In setting mode 1, push and hold the BS1 (MODE button) for more than 5 seconds.
Setting mode 2 is entered and H1P lights.
(2) Push the BS2 (SET button) several times and match the LED display with the Setting No.
you want.
(3) Push the BS3 (RETURN button) one time, and the present setting content is displayed.
Push the BS2 (SET button) several times and match the LED display with the setting
content (as shown on next page) you want.
(4) Push the BS3 (RETURN button) two times.
Returns to (1).
(5) Push the BS1 (MODE button) one time.
Returns to the setting mode 1 and turns H1P off.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin Super Multi Plus E-Series FFQ50B8V1B and is the answer not in the manual?

Daikin Super Multi Plus E-Series FFQ50B8V1B Specifications

General IconGeneral
BrandDaikin
ModelSuper Multi Plus E-Series FFQ50B8V1B
CategoryAir Conditioner
LanguageEnglish

Related product manuals