EasyManuals Logo

Daikin Super Multi Plus E-Series FFQ50B8V1B User Manual

Daikin Super Multi Plus E-Series FFQ50B8V1B
492 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #421 background imageLoading...
Page #421 background image
SiBE18-821_C Troubleshooting for Outdoor Unit
Troubleshooting 409
7.24 Low Pressure Drop due to Refrigerant Shortage or
Electronic Expansion Valve Abnormality
Remote
Controller
Display
U0
Method of
Malfunction
Detection
Refrigerant shortage is detected by discharge pipe thermistor and low pressure saturation
temperature.
Malfunction
Decision
Conditions
Microcomputer judge and detect if the system is short of refrigerant.
★
The error is not decided while the operation continues.
Supposed
Causes
îš„
Refrigerant shortage or refrigerant system clogging (incorrect piping)
îš„
Defective low pressure sensor
îš„
Defective main PCB (A1P)
îš„
Defective thermistor (R3T)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin Super Multi Plus E-Series FFQ50B8V1B and is the answer not in the manual?

Daikin Super Multi Plus E-Series FFQ50B8V1B Specifications

General IconGeneral
BrandDaikin
ModelSuper Multi Plus E-Series FFQ50B8V1B
CategoryAir Conditioner
LanguageEnglish

Related product manuals