SiBE18-821_C Troubleshooting with LED
Troubleshooting 333
BRC7E530W, BRC7F532F, BRC7EA63W
In case of wireless remote controller, a signal receiver PCB and a display PCB are installed on
indoor unit.
When the error occurs, the operation lamp on the display PCB blinks.
Caution: When operation stops suddenly and the operation lamp blinks, it could be "operation mode
conflict".
Check followings;
Are the operation modes all the same for the indoor units connected to multi system outdoor
unit?
If not, set all the indoor units to the same operation mode and confirm that the operation lamp is
not blinking.
Moreover, when the operation mode is automatic, set all the indoor unit operation mode as
"cooling" or "heating" and check again if the operation lamp is normal.
If the lamp stops blinking after the above steps, there is no malfunction.
★
Operation stops and operation lamp blinks only for indoor unit which different operation mode
is set later. (The first set operation mode has priority.)
1.3.2 Service Monitor
The indoor unit has one green LED (LED A) on the control PCB. When the microcomputer
works in order, the LED A blinks.
BRC1E51A7
Operation lamp (green)
(R12852)
+ The error or warning message also blinks on
the basic screen.