EasyManuals Logo

Daikin Super Multi Plus E-Series FFQ50B8V1B User Manual

Daikin Super Multi Plus E-Series FFQ50B8V1B
492 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #352 background imageLoading...
Page #352 background image
Service Check Function SiBE18-821_C
340 Troubleshooting
2.1.3 ARC433 Series Remote Controller
Check Method 1 1. When the timer cancel button is held down for 5 seconds, “
00
” indication appears on the
temperature display section.
2. Press the timer cancel button repeatedly until a long beep sounds.
The code indication changes in the sequence shown below.
<ARC433B41>
<ARC433B67, B69, B70>
Note: 1. A short beep “pi” and two consecutive beeps “pi pi” indicate non-corresponding codes.
2. To return to the normal mode, hold the timer cancel button down for 5 seconds. When the
remote controller is left untouched for 60 seconds, it also returns to the normal mode.
TIMER
ON
CANCEL
OFF
TIMER CANCEL button
(R11506)
< ARC433 Series >
No. Code No. Code No. Code
1 00 12 F6 23 A1
2 U4 13 C7 24 E1
3 L5 14 A3 25 UA
4 E6 15 H8 26 UH
5 H6 16 H9 27 P4
6 H0 17 C9 28 L3
7 A6 18 C4 29 L4
8 E7 19 C5 30 H7
9 U0 20 J3 31 U2
10 F3 21 J6 32 EA
11 A5 22 E5 33 AH
No. Code No. Code No. Code
1 00 12 C7 23 H0
2 U4 13 H8 24 E1
3 F3 14 J3 25 P4
4 E6 15 A3 26 L3
5 L5 16 A1 27 L4
6 A6 17 C4 28 H6
7 E5 18 C5 29 H7
8 F6 19 H9 30 U2
9 C9 20 J6 31 UH
10 U0 21 UA 32 EA
11 E7 22 A5 33 AH

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin Super Multi Plus E-Series FFQ50B8V1B and is the answer not in the manual?

Daikin Super Multi Plus E-Series FFQ50B8V1B Specifications

General IconGeneral
BrandDaikin
ModelSuper Multi Plus E-Series FFQ50B8V1B
CategoryAir Conditioner
LanguageEnglish

Related product manuals