www.DaikinApplied.com 111 IOM 1207-6 • TRAILBLAZER
®
MODEL AGZ CHILLERS
Figure 85: LCD Display
Table 76: Display Data
No Name  Content
1
Operation Mode
Menus
MODE Displayed when in Mode Selection.
MONITR Displayed when in Monitor Mode.
VERIFY Indicates the Verify Menu
PRMSET Displayed when in Parameter Setting Mode.
A.TUNE Displayed during Auto-Tuning.
SETUP Displayed when in Setup Mode.
2
DriveWorksEZ
Function Selection
DWEZ Displayed when DriveWorksEZ is set to enable. (A1-07 = 1 or 2)
3 Mode Display Area
DRV Displayed when in Drive Mode.
PRG Displayed when in Programming Mode
4 Ready Rdy Indicates the drive is ready to run.
5 Data Display Displays specic data and operation data.
6
Frequency
Reference
Assignment
<1>
OPR Displayed when the frequency reference is assigned to the LCD Operator Option
AI Displayed when the frequency reference is assigned to the Analog Input of the drive
COM
Displayed when the frequency reference is assigned to the MEMOBUS/Modbus Communication
Inputs of the drive
OP Displayed when the frequency reference is assigned to an Option Unit of the drive.
RP Displayed when the frequency reference is assigned to the Pulse Train Input of the drive
7 LO/RE Display <2>
RSEQ Displayed when the run command is supplied from a remote source.
LSEQ Displayed when the run command is supplied from the operator keypad.
RREF Displayed when the run command is supplied from a remote source.
LREF Displayed when the run command is supplied from the operator keypad
8 Function Key 1(F1)
JOG Pressing [F1} executes the Jog function.
HELP Pressing [F1] displays the Help menu.
Pressing [F1] scrolls the cursor to the left.
HOME Pressing [F1] returns to the top menu (Frequency Reference).
ESC Pressing [F1] returns to the previous display
9 FWD/REV
FWD Indicates forward motor operation.
REV Indicates reverse motor operation.
10 Function Key 2 (F2)
FWD/REV Pressing [F2] switches between forward and reverse
DATA Pressing [F2] scrolls to the next display
Pressing [F2] scrolls the cursor to the right
RESET Pressing [F2] resets the existing drive fault error