www.DaikinApplied.com 121 IOM 1207-6 • TRAILBLAZER
®
MODEL AGZ CHILLERS
Table 83: LONWORKS Network Parameters
Parameter Default Value
8-02 Control Source
Option A [3]/During initial pow er-up, the frequency converter automatically
sets this parameter to Option A [3] if it detects a valid eldbus option
installed in slot A
FC Port [1]
11-0 Neuron ID Variable/This is the neuron ID of the Lonw orks module.
Variable/This item w ill be blank if the
communication module is not commissioned.
11-10 Drive Prole VSD Prole [0]/This parameter indicates the LONMARK functional prole VSD Prole [0]
11-15 LON
Warning Word
(0-FFFF)/This parameter contains LON specic w arnings.
Bit Status
0 Internal Fault
1 Internal Fault
2 Internal Fault
3 Internal Fault
4 Internal Fault
5 Reserved
6 Reserved N/A
7 Reserved
8 Reserved
9 Invalid type change for changeable types
10 Initialization error
11 Internal communication error
12 Software revision mismatch
13 Bus not active
14 Option not present
15 LON input (nvi/nci) exceeds limits
11-17 XIF Revision
0 N/A/This parameter contains the version of the external interface le on
the Neuron C chip on the LON option
0 N/A
11-18 LonWorks
Revision
0 N/A/This parameter contains the softw are version o the application
program on the Neuron C chip on the LON option.
0 N/A
11-21 Store Data
Values
O [0] or Store all setups [2]/This parameter is used to activate storing of
data in non-volatile memory.
When activated (set to [2] Store all setups), all
parameters are stored in EEPROM; the value
returns to [2] O w hen all parameter values
have been stored.
Table 84: MS Service LED - Red
Situation Description
Congured state (normal operation) ½ sec. ON, then continuously OFF The node is congures and running normally.
Non-congured state Flashing ½ Hz
Node is not congures but has an application.
Proceed w ith loading node.
Applicationless state
1 sec. ON, 2 sec. OFF, then
continuously ON
Node has no application, the LonWorks option
needs replacing or reprogramming
Watchdog resets Short ash about each 3 sec.
Indicates problem w ith application. The
LonWorks option needs replacing.
Faulty hardware Steady ON or OFF The LonWorks option needs replacing.