20 | Electrical installation
Installer and user reference guide
103
RXYSA4~6A7V/Y1B
VRV 5-S system air conditioner
4P600330-1 – 2020.01
Transmission wiring specification and limits
(a)
Maximum wiring length
(distance between outdoor and furthest indoor unit)
300m
Total wiring length
(sum of distances between outdoor and all indoor units)
600m
(a)
If the total transmission wiring exceeds these limits, communication errors might occur.
No secondary branchings are allowed after any transmission wire branching.
A Outdoor unit
B Indoor unit
C Central user interface (etc...)
a Main line
b1, b2, b3 Branch lines
c1, c2 No branch is allowed after branch
Example:
e
d
F1/F2
(16 V)
F1/F2
(16 V)
220-240 V
1~ 50 Hz
c
a
Y
V
b
220-240 V
1~ 50 Hz
380-415 V
3N~ 50 Hz
a Main switch
b Earth connection
c Power supply wiring (including earth) (EMC shielded cable)
F1/F2 Transmission wiring (EMC shielded cable)
V Outdoor unit (RXYSA4~6_V)
Y Outdoor unit (RXYSA4~6_Y)
d Indoor unit
e User interface