20 | Electrical installation
Installer and user reference guide
104
RXYSA4~6A7V/Y1B
VRV 5-S system air conditioner
4P600330-1 – 2020.01
20.1.3 Guidelines when knocking out knockout holes
NOTICE
Precautions when making knockout holes:
Avoid damaging the casing.
After making the knockout holes, we recommend you remove the burrs and paint
the edges and areas around the edges using repair paint to prevent rusting.
When passing electrical wiring through the knockout holes, wrap the wiring with
protective tape to prevent damage.
b
c
a
a Knockout hole
b Burr
c Sealant etc.
20.1.4 Guidelines when connecting the electrical wiring
Keep the following in mind:
If stranded conductor wires are used, install a round crimp-style terminal on the
end of the wire. Place the round crimp-style terminal on the wire up to the
covered part and fasten the terminal with the appropriate tool.
b a
a Stranded conductor wire
b Round crimp-style terminal
Use the following methods for installing wires:
Wire type Installation method
Single-core wire
c b
c
aa
A
AA´
a Curled single-core wire
b Screw
c Flat washer