SiE39-404 Troubleshooting by Indication on the Remote Controller
Troubleshooting 187
2.12 CJ Indoor Unit: Malfunction of Thermostat Sensor in
Remote Controller
Remote
Controller
Display
CJ
Applicable
Models
AII indoor unit models
Method of
Malfunction
Detection
Malfunction detection is carried out by temperature detected by remote controller air
temperature thermistor. (Note1)
Malfunction
Decision
Conditions
When the remote controller air temperature thermistor becomes disconnected or shorted while
the unit is running.
Supposed
Causes
Defect of remote controller thermistor
Defect of remote controller PC board
Troubleshooting
Note: In case of remote controller thermistor malfunction, unit is still operable by suction air thermistor
on indoor unit.
2: Refer to thermistor resistance / temperature characteristics table on P311.
Turn power supply OFF, then
power ON again.
Is "CJ"
displayed on the remote
controller?
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
YES
NO
Caution
Replace remote controller.
External factor other than
equipment malfunction.
(for example, noise etc.)
(V2787)

Table of Contents

Other manuals for Daikin VRV II RXYQ5MY1B

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin VRV II RXYQ5MY1B and is the answer not in the manual?

Daikin VRV II RXYQ5MY1B Specifications

General IconGeneral
SeriesVRV II
ModelRXYQ5MY1B
TypeHeat Pump
Cooling Capacity (kW)14.0
Heating Capacity (kW)16.0
RefrigerantR410A
Operating Temperature (Cooling)-5 to 46 °C
Sound Pressure Level (Outdoor Unit)58 dB(A)
Power Supply380-415V, 50Hz, 3-Phase

Related product manuals