5 Installation
Installation and operation manual
18
RYYQ+RYMQ+RXYQ8~20T7Y1B
VRV IV system air conditioner
4P370473-1C – 2016.07
5.6.4 To charge refrigerant: Flow chart
For more information, see "5.6.5To charge refrigerant"on page20.
Pre-charging refrigerant
Step 1
Calculate additional refrigerant charge amount: R (kg)
Refrigerant overcharge happened, recover
refrigerant to reach R=Q
Step 2+3
Open valves C, D and B to the liquid and equalising line
Charge the equalising line to maximally 0.05 MPa, then close valve C and
disconnect its connection to the manifold. Continue pre-charging through
the liquid line only
Execute pre-charging amount: Q (kg)
Step 4a
Close valves D and B
Charging is finished
Fill in the amount on the additional
refrigerant charge label
Input the additional refrigerant amount via
setting [2-14]
Go to test run
Step 4b
Close valves D and B
R=Q R>QR<Q
Continued on next page >>
p
<
p
>
R410AN2
C
D
A B