6 Configuration
Installation and operation manual
27
RYYQ+RYMQ+RXYQ8~20T7Y1B
VRV IV system air conditioner
4P370473-1C – 2016.07
What How
Changing the value of the
selected setting in mode2
Once mode 2 is selected (push BS1
for more than 5 seconds) you can
select the wanted setting. It is done
by pushing BS2.
Accessing the selected setting's value
is done by pushing BS3 1 time.
Now BS2 is used to select the
required value of the selected setting.
When the required value is selected,
you can define the change of value
by pushing BS3 1 time.
Press BS3 again to start operation
according to the chosen value.
6.1.7 Mode 1: Monitoring settings
[1‑0]
Shows whether the unit you check is a master, slave 1 or slave 2
unit.
The master unit should be used to input field settings in
mode2.
[1‑0] Description
No indication Undefined situation.
0 Outdoor unit is master unit.
1 Outdoor unit is slave1 unit.
2 Outdoor unit is slave2 unit.
[1‑1]
Shows the status of low noise operation.
[1‑1] Description
0 Unit is currently not operating under low noise
restrictions.
1 Unit is currently operating under low noise
restrictions.
[1‑2]
Shows the status of power consumption limitation operation.
[1‑2] Description
0 Unit is currently not operating under power
consumption limitations.
1 Unit is currently operating under power
consumption limitation.
[1‑5] [1‑6]
Shows:
[1‑5]: The current T
e
target parameter position.
[1‑6]: The current T
c
target parameter position.
[1‑10]
Shows the total number of connected indoor units.
[1‑13]
Shows the total number of connected outdoor units (in case of
multiple outdoor system).
[1‑17] [1‑18] [1‑19]
Shows:
[1‑17]: The latest malfunction code.
[1‑18]: The 2nd last malfunction code.
[1‑19]: The 3rd last malfunction code.
[1‑29] [1‑30] [1‑31]
Shows the estimated leaked refrigerant amount (kg) based on:
[1‑29]: The latest leak detection operation.
[1‑30]: The 2nd last leak detection operation.
[1‑31]: The 3rd last leak detection operation.
[1‑34]
Shows the remaining days till the next automatic leak detection (if
automatic leak detection function is activated).
[1‑35] [1‑36] [1‑37]
Shows the result of:
[1‑35]: The latest automatic leak detection execution.
[1‑36]: The 2nd last automatic leak detection operation.
[1‑37]: The 3rd last automatic leak detection operation.
[1‑35] [1‑36] [1‑37] Description
1 Normal execution of leak detection operation
occurred.
2 Operation conditions during leak detection
operation were not satisfied (ambient
temperature was not within the limitations).
3 Malfunction occurred during leak detection
operation.
If Then the estimated leaked refrigerant
amount is displayed in
[1‑35]=1 [1‑29]
[1‑36]=1 [1‑30]
[1‑37]=1 [1‑31]
[1‑38] [1‑39]
Shows:
[1‑38]: The number of RA DX indoor units connected to the
system.
[1‑39]: The number of Hydrobox (HXY080/125) indoor units
connected to the system.
[1‑40] [1‑41]
Shows:
[1‑40]: The current cooling comfort setting.
[1‑41]: The current heating comfort setting.
6.1.8 Mode 2: Field settings
[2‑0]
Cool/Heat selection setting.
[2‑0] Description
0 (default) Each individual outdoor unit can select Cool/
Heat operation (by Cool/Heat selector if
installed), or by defining master indoor user
interface (see setting [2‑83] and the operation
manual).
1 Master unit decides Cool/Heat operation when
outdoor units are connected in multiple system
combination
(a)
.
2 Slave unit for Cool/Heat operation when
outdoor units are connected in multiple system
combination
(a)
.
(a) It is necessary to use the optional external control adaptor
for outdoor unit (DTA104A61/62). See the instruction
delivered with the adaptor for further details.