Troubleshooting by Error Code SiUS331604E
165 Service Diagnosis
4.18 Remote Controller Thermistor Abnormality
Error Code CJ
Applicable
Models
All indoor units
Method of Error
Detection
Error detection is carried out by the temperature detected by the remote controller thermistor. (See
note.)
Error Decision
Conditions
When the remote controller thermistor becomes disconnected or shorted while the unit is running.
Error code is displayed but the system operates continuously.
Supposed
Causes
Defective room temperature thermistor in remote controller
Defective remote controller PCB
Troubleshooting
Note: 1: How to delete “history of error codes”.
Press the “ON/ OFF” button for 4 seconds and more while the error code is displayed in the
inspection mode.
Clear the error code history.
(While in inspection mode,
press and hold the “ON/OFF”
button for a period of 4
seconds or more.)
YES
Is CJ
displayed on the remote
controller?
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
NO
Replace the remote
controller.
External factor other than
equipment error.
(for example, noise etc.)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin VRV IV-S RXTQ-TAVJU Series and is the answer not in the manual?

Daikin VRV IV-S RXTQ-TAVJU Series Specifications

General IconGeneral
TypeHeat Pump
SeriesVRV IV-S
ModelRXTQ-TAVJU
RefrigerantR-410A
Indoor Unit TypeCeiling Cassette, Wall Mounted
Dimensions (Indoor Unit)Varies by model
Dimensions (Outdoor Unit)Varies by model
Operating Temperature Range (Cooling)-5°C to 46°C
Power Supply208-230V, 60Hz
Maximum Height Difference50m

Related product manuals