16 Configuration
Installation and operation manual
32
RXYSQ4~6T8V/YB(*)
VRV IV-S system air conditioner
4P482275-1B – 2020.10
Setting
(= binary)
Value
Description
[2‑26]
Low noise operation start time.
This setting is used in conjunction with setting [2‑22].
20h00
(default)
22h00
24h00
[2‑27]
Low noise operation stop time.
This setting is used in conjunction with setting [2‑22].
6h00
7h00
(default)
8h00
[2‑30]
Power consumption limitation level (step1) via the external control
adaptor (DTA104A61/62).
If the system needs to be running under power consumption
limitation conditions when an external signal is sent to the unit, this
setting defines the level power consumption limitation that will be
applied for step1. The level is according to the table.
60%
(default)
70%
80%
[2‑31]
Power consumption limitation level (step2) via the external control
adaptor (DTA104A61/62).
If the system needs to be running under power consumption
limitation conditions when an external signal is sent to the unit, this
setting defines the level power consumption limitation that will be
applied for step2. The level is according to the table.
30%
(default)
40%
50%
[2‑32]
Forced, all time, power consumption limitation operation (no
external control adaptor is required to perform power consumption
limitation).
If the system always needs to be running under power
consumption limitation conditions, this setting activates and defines
the level power consumption limitation that will be applied
continuously. The level is according to the table.
(default)
Function not active.
Follows [2‑30] setting.
Follows [2‑31] setting.
[2‑38]
Type of indoor units
After changing this setting, you have to power OFF the system,
wait for 20s, and then power ON again. If not, the setting will not
be processed and malfunction codes might occur.
(default)
VRVDX indoor units installed
RADX indoor units installed
[2‑41]
Cooling comfort setting.
This setting is used in conjunction with setting [2‑8].
Eco
(default)
Mild
Quick
Powerful
[2‑42]
Heating comfort setting.
This setting is used in conjunction with setting [2‑9].
Eco
(default)
Mild
Quick
Powerful