20 Technical data
Installation and operation manual
36
RXYSQ4~6T8V/YB(*)
VRV IV-S system air conditioner
4P482275-1B – 2020.10
Main code Cause Solution
Improper type of indoor units are connected. Check the type of indoor units that are currently connected.
If they are not proper, replace them with proper ones.
Incorrect interconnections between units. Connect interconnections F1 and F2 of the connected BP
unit correctly to the outdoor unit's PCB (TO BP UNIT). Make
sure that the communication with the BP unit is enabled.
The stop valve of an outdoor unit is left closed.
The piping and wiring of the specified indoor unit are not
connected correctly to the outdoor unit.
Open the stop valve on both the gas and liquid side.
Confirm that the piping and wiring of the specified indoor
unit are connected correctly to the outdoor unit.
20 Technical data
A subset of the latest technical data is available on the regional Daikin website (publicly accessible). The full set of latest technical data is
available on the Daikin Business Portal (authentication required).
20.1 Service space: Outdoor unit
When mounting units side by side, the piping route must be to the front, to the back or downwards. In this case the piping route to the side is
not possible.
When mounting the units side by side and routing the piping to the back, you must keep a distance of ≥250mm between the units (instead of
≥100mm as shown on the figures below).
Single unit ( ) | Single row of units ( )
See figure1 on the inside of the front cover of this manual.
A,B,C,D Obstacles (walls/baffle plates)
E Obstacle (roof)
a,b,c,d,e Minimum service space between the unit and obstacles A, B, C, D and E
e
B
Maximum distance between the unit and the edge of obstacle E, in the direction of obstacle B
e
D
Maximum distance between the unit and the edge of obstacle E, in the direction of obstacle D
H
U
Height of the unit
H
B
,H
D
Height of obstacles B and D
1 Seal the bottom of the installation frame to prevent discharged air from flowing back to the suction side through the bottom of the unit.
2 Maximum two units can be installed.
Not allowed
Multiple rows of units ( )
See figure2 on the inside of the front cover of this manual.
Stacked units (max. 2 levels) ( )
See figure3 on the inside of the front cover of this manual.
A1=>A2 (A1) If there is danger of drainage dripping and freezing between the upper and lower units…
(A2) Then install a roof between the upper and lower units. Install the upper unit high enough above the lower unit to prevent ice buildup at the
upper unit's bottom plate.
B1=>B2 (B1) If there is no danger of drainage dripping and freezing between the upper and lower units…
(B2) Then it is not required to install a roof, but seal the gap between the upper and lower units to prevent discharged air from flowing back to the
suction side through the bottom of the unit.