11.4 Malfunction codes
Incaseamalfunctioncodeappearsontheindoor
unituserinterfacedisplay,contactyourinstaller
andinformthemalfunctioncode,theunittype,and
serialnumber(youcanndthisinformationonthe
nameplateoftheunit).
Foryourreference,alistwithmalfunctioncodesis
provided.Yo u can,dependingonthelevelofthe
malfunctioncode,resetthecodebypushingthe
ON/OFFbutton.Ifnot,askyourinstallerforadvice.
Malfunction
code
Contents
Main code
A0
Externalprotectiondevicewasactivated
a1
EEPROMfailure(indoor)
A3
Drainsystemmalfunction(indoor)
A6
Fanmotormalfunction(indoor)
A7
Swingapmotormalfunction(indoor)
A9
Expansionvalvemalfunction(indoor)
AF
Drainmalfunction(indoorunit)
Ah
Filterdustchambermalfunction(indoor)
AJ
Capacitysettingmalfunction(indoor)
C1
TransmissionmalfunctionbetweenmainPCBand
subPCB(indoor)
C4
Heatexchangerthermistormalfunction
(indoor;liquid)
C5
Heatexchangerthermistormalfunction
(indoor;gas)
C9
Suctionairthermistormalfunction(indoor)
CA
Dischargeairthermistormalfunction(indoor)
CE
Movementdetectororoortemperaturesensor
malfunction(indoor)
CJ
Userinterfacethermistormalfunction(indoor)
e1
PCBmalfunction(outdoor)
e3
Highpressureswitchwasactivated
e4
Lowpressuremalfunction(outdoor)
e5
Compressorlockdetection(outdoor)
e6
Compressordamagealarm
e7
Fanmotormalfunction(outdoor)
e9
Electronicexpansionvalvemalfunction(outdoor)
F3
Dischargetemperatureoroverloadprotectorwas
activated(outdoor)
f4
Abnormalsuctiontemperature(outdoor)
f6
Refrigerantoverchargedetection
H3
Highpressureswitchwasactivated
H5
Overloadprotectormalfunction
H7
Fanmotortrouble(outdoor)
H9
Ambienttemperaturesensormalfunction(outdoor)
J1
Pressuresensormalfunction
J3
Dischargetemperaturesensormalfunction(outdoor)
J5
Suctiontemperaturesensormalfunction(outdoor)
J6
De-icingtemperaturesensormalfunction(outdoor)
J7
Liquidtemperaturesensor(aftersubcoolHE)
malfunction(outdoor)
J8
Liquidtemperaturesensor(coil)malfunction(outdoor)
Malfunction
code
Contents
Main code
J9
Gastemperaturesensor(aftersubcoolHE)
malfunction(outdoor)
JA
Highpressuresensormalfunction(S1NPH)
JC
Lowpressuresensormalfunction(S1NPL)
L1
INVcircuitabnormal
L4
Fintemperatureabnormal
L5
INVcircuitfaulty
L8
Compressorovercurrentdetected
L9
INVcompressorstartupabnormal
Lc
INVcircuittransmissiontrouble
P1
INVunbalancedpowersupplyvoltage
p2
Autochargeoperationrelated
P4
Finthermistormalfunction
p8
Autochargeoperationrelated
p9
Autochargeoperationrelated
pj
Capacitysettingmalfunction(outdoor)
u0
Refrigerantshortagewarning
u2
INVvoltagepowershortage
u3
Systemtestrunnotyetexecuted
u4
Faultywiringindoor/outdoor
u5
Abnormaluserinterface-indoorcommunication
u8
Abnormalmain-subuserinterfacecommunication
u9
Systemmismatch.Wrongtypeofindoorunitscombined.
Indoorunitmalfunction.
ua
Connectionmalfunctionoverindoorunitsortype
mismatch
uc
Centralizedaddressduplication
ue
Malfunctionincommunicationcentralizedcontrol
device-indoorunit
uf
Autoaddressmalfunction(inconsistency)
uh
Autoaddressmalfunction(inconsistency)