Troubleshooting by Indication on the Remote Controller
140
Troubleshooting
Note:
1. Compare the resistance values of the discharge pipe
thermistor with measurements of a surface
thermometer.
(For temperature and resistance characteristics of a
thermistor, refer to P.371.)
2. Compare the discharge pipe temperature checked
by the Service
Checker with the resistance of the thermistor (refer to
1).
Refer to P.351.
NO
YES
YES
Replace the
discharge pipe
thermistor.
Are
discharge
pipe thermistor
characteristics
normal?
(1)
NO
Replace the main
PCB.
Is PCB
detection temperature
normal?
(2)
· The discharge pipe thermistor is normal and the
main PCB temperature detection is also normal.
· In fact, discharge pipe temperature is rising.
CHECK 3
Caution
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
may be damaged.
Connect the Service
Checker.
Restart operation after
resetting operation.