Troubleshooting by Indication on the Remote Controller
141
Remote Controller Display
F3
Applicable Models
VRVII and II-S Series
Method of Error Detection
Abnormality is detected according to the temperature
detected by the discharge pipe thermistor.
Error Decision Conditions
When the discharge pipe temperature rises to an
abnormally high level
When the discharge pipe temperature rises suddenly
Supposed Causes
Defective discharge pipe thermistor
Defective connection of discharge pipe thermistor