Troubleshooting by Indication on the Remote Controller
255
Note:
3: Compare the thermistor resistance with surface
thermostat measurements.
4: Compare the suction pipe temperature checked by
the Service Checker with measurements obtained in
3 above.
Refer to P.348.
Refer to P.351.
Refer to P.372.
NO
YES
YES
Are
characteristics of
the suction pipe
thermistor and the heat
exchanger
thermistor
normal?
(3)
Replace the
thermistor.
NO
Is PCB
detection
temperature normal?
(4)
Replace the main
PCB.
CHECK 3
In heating
Connect the Service
Checker.
After resetting
operation with a remote
controller, restart
operation.
CHECK 2
CHECK 3
CHECK 12